Home/Blog/Motor Circuits on the Exam: Why Candidates Miss Them

Motor Circuits on the Exam: Why Candidates Miss Them

Motor questions use table currents for some things and nameplate currents for others, and the percentages change by device. The four-step method, a worked example and the traps.

Article 430 breaks the habit most electricians bring to the exam: that one current number drives everything. For motors, two numbers matter, they come from different places, and each part of the circuit uses its own percentage. Once that is clear the questions are mechanical.

Two currents

Table current. 430.6(A)(1) says that for sizing conductors, switches and branch-circuit short-circuit and ground-fault protection, you use the full-load current from Tables 430.247 (DC), 430.248 (single-phase), 430.249 (two-phase) and 430.250 (three-phase), based on horsepower and voltage. Not the nameplate.

Nameplate current. 430.6(A)(2) says that for sizing overload protection you use the motor's nameplate current rating.

Candidates who use the nameplate for conductors get a smaller conductor than the exam wants; candidates who use the table for overloads get the wrong setting. Memorise which is which before anything else.

The four steps

  1. Conductors, 430.22. 125 percent of the table full-load current for a single motor. Pick the conductor from Table 310.16 at the 75 degree column (or 60 degree where terminations require it).
  2. Overloads, 430.32. For a continuous-duty motor over one horsepower: 125 percent of nameplate current if the motor has a service factor of 1.15 or more or a temperature rise of 40 degrees or less; otherwise 115 percent. If that setting does not let the motor start, 430.32(C) allows up to 140 or 130 percent.
  3. Branch-circuit short-circuit and ground-fault protection, 430.52. Take the percentage from Table 430.52 for the device type: for a typical squirrel-cage AC motor, 300 percent for a nontime-delay fuse, 175 percent for a dual-element time-delay fuse, 250 percent for an inverse-time breaker, applied to the table current. If the result is not a standard size in 240.6, the exception allows the next standard size up.
  4. Disconnect, 430.102 and 430.110. Within sight of the motor and controller unless the exceptions apply, rated at least 115 percent of the table current.

Worked example

A 10 horsepower, 230 volt, three-phase squirrel-cage motor, continuous duty, nameplate 26 amperes, service factor 1.15, protected by an inverse-time circuit breaker.

Table current. Table 430.250, 10 horsepower at 230 volts: 28 amperes.

Conductors. 28 × 1.25 = 35 amperes. Table 310.16, 75 degree column: 10 AWG copper is 35 amperes. 10 AWG.

Overloads. Nameplate 26 amperes × 1.25 (service factor 1.15) = 32.5 amperes maximum setting.

Branch-circuit protection. Inverse-time breaker: 28 × 2.5 = 70 amperes. 70 is a standard size in 240.6, so a 70 ampere breaker. If the result had been 65 amperes, the exception would allow the next standard size, 70.

Disconnect. 28 × 1.15 = 32.2 amperes minimum.

Notice that a 70 ampere breaker protects 10 AWG conductors rated 35 amperes. That looks wrong to candidates who have 240.4 in their heads; it is right because 240.4(G) sends motor circuits to Article 430, where the overloads protect the conductors and the breaker only handles short circuits and ground faults.

Several motors on one feeder

430.24: feeder conductors carry 125 percent of the largest motor's table current plus the sum of the full-load currents of the rest. 430.62: the feeder protection is the largest branch-circuit protective device for any motor in the group plus the full-load currents of the other motors, not exceeding that total. Exams love a two-motor feeder question because it tests whether you know that only the largest motor gets the 125 percent.

The traps

Nameplate for conductors. The most common miss. If the question gives both a nameplate and a horsepower, the horsepower is there so you can use the table.

Wrong table. 430.248 is single-phase, 430.250 is three-phase. Check the phase before reading a number.

Wrong percentage. The 250 percent is for inverse-time breakers; a time-delay fuse is 175. The question tells you the device.

Next size up. Allowed for the branch-circuit device under 430.52(C)(1) Exception No. 1, not for the overload setting.

Service factor. A service factor of 1.15 or a 40 degree rise means 125 percent for overloads; anything else means 115. Read the motor data twice.

Practice

Work ten motor problems in a row, changing horsepower, voltage, phase and device type each time, with the four steps written at the top of the page. Then ten more without the steps written down. After that, motor questions become the fastest calculation on the exam, because every one follows the same path.